| Modek
GRP and PC Installation Specs
Research has found that most wind damage associated with translucent
roof sheets is as a result of sheets being pulled over the fastenings.
This
is normally related to the following aspects of the installation:
-
Purlin or girt spacings
- Diameter
of fastening washer
- Frequency
and accuracy of fastenings
FIXING
CONFIGURATIONS
It
is not practical to give standard purlin spacings and fastening
specifications for all applications, but as a guide, the following
recommendations will apply to most standard installations:
| GUIDE
TO MAXIMUM SUPPORT CENTRES
|
| Profile
Depth |
Chequerboard |
Continuous
Run |
| |
|
|
| 18
- 25 mm |
1
200 mm |
900
mm |
| 26
- 30 mm |
1
500 mm |
1
000 mm |
| 31
- 55 mm |
1
800 mm |
1
500 mm |
| |
For
side cladding with all profiles, the maximum girt spacing should
be 1 500 mm.
- The
term chequerboard refers to MODEK sheets laid where the side and
end laps of each sheet are fixed to, and supported by, an adjacent
metal or FC sheet.
- The
term continuous run refers to sheets laid in a pattern where they
are fixed side-by-side to one-another, or in a verge to verge
configuration.
FIXING
DETAILS
Roof
Pitch < 10°:
- All
MODEK sheets are to be fastened to supports through each crown
of the profile (primary fixings), and side stitched to adjacent
sheet not exceeding 400 mm (secondary fixings).
Roof
Pitch > 10°:
- All
MODEK sheets can be fastened to supports in the trough of the
profile (primary fixings), and side stitched to adjacent sheet
not exceeding 500 mm (secondary fixings).
Primary
Fixings:
- All
primary fixings to be used in conjunction with a metal washer
with suitable sealing ring or soft washer under. The diameter
of washer to be minimum 20 mm up to 30 mm. It is advisable
to apply a bead of silicone under the washer to prevent possible
leaks at fixing points. Primary
fixings to be specified by specialist for either steel or timber
supports. Note:
PVC soft washers NOT to be used with MODEK PC sheets.
- To
avoid distorting the sheet profile, packing pieces should be located
between the sheet and the supporting structure, when fastening
through the crown.
Secondary
Fixings:
- Side
stitching to be M6 roofing bolts or "Bulb-tite" fasteners.
Self tapping screws and "pop rivets" are unsuitable for use as
side stitching fasteners.
General
Notes:
- If
fastenings are not fixed square onto the sheets, the edge of a
skew washer can impart a guillotine effect on the sheet and cause
failure at lower loads.
- Do
not locate a primary fixing closer than 50 mm to the end of a
MODEK sheet.
-
All fastening holes to be drilled through the MODEK sheet with
a 1 mm - 2 mm clearance for GRP and a 2 mm -5 mm clearance
for PC. This applies to sheets of up to 3.6 metre length.
Longer lengths will require greater clearance at fastening holes.
Calculate clearance required for each application based on coefficient
of linear expansion: GRP = 24 x 10-6M/°C
; PC = 67 x 10-6M/°C
- All
fastenings to be tightened sufficiently, but to allow for thermal
movement of MODEK sheeting.
-
The cantilever, or eaves overhang, should not exceed 200 mm.
WEATHER
TIGHTNESS:
The
profile of the MODEK sheet should match the end and side laps of
the adjacent metal or FC roof sheets. These laps should be
sealed with a sealing mastic or a closed cell white self-adhesive
tape by applying the sealant to the bottom sheet before laying the
top sheet over. Where
MODEK sheets are installed in a continuous run, the side and end
laps should be double sealed with a sealing mastic or a closed cell
white self-adhesive tape to avoid dirt and moisture getting into
the laps.
Note:
- PVC-based
sealant or strips NOT to be used with MODEK PC sheets, all sealants
/ tapes to be PC compatible.
- Side
laps should be installed facing away from prevailing winds.
- Sealed
end laps should be 250 mm minimum on roofs < 10° pitch and
150 mm minimum on roofs > 10° pitch. Note:
Unsealed end laps are not permitted on roofs of < 10° pitch
(SABS 0400-1990).
- Unsealed
end laps should be between 150 mm and 250 mm minimum on roofs
> 10° pitch.
Safety:
When working on a roof for installation or maintenance purposes,
do not walk on MODEK roof lights. Always use crawling boards to
distribute your weight evenly. It is advised to use appropriate
fall arrest safety equipment.
Avoid working on a roof in excessively windy conditions, and take
precautions to avoid MODEK sheets being damaged by wind when handling.
Use gloves when handling MODEK sheets.
Longitudinal Bending Radii:
MODEK sheets are only supplied in straight lengths. As a general
rule the S-rib profiles are suitable to be used for curved applications,
such as barrelvaults, providing that a minimum bending radius of
4.0 meters is adhered to. Box rib profiles may be used in curved
applications providing that a minimum bending radius of 14.0 meters
is adhered to.
Should you require to calculate the radius of a curved roof, or
the length of a curved sheet, the following formulae would apply:
Calculation of Radius:
Calculation for Length of Sheets:
On all curved roof applications, sheets must be fixed over one or
more intermediate purlins as may be required.
WIND LOADS
Experience has shown that consideration of wind loads, though important,
is often overlooked. For this reason, a few words of advice on this
subject are included here to encourage the use of adequate installation
and fixing procedures.
Beware of areas which may be in the immediate wake of obstructions
such as a tower or surface which may be swept by high winds. Beware
also of potential high wind speeds in narrow gaps between buildings.
Negative surface loads which may occur on the lee-ward side of a
roof should also be taken into account.
Where excessive overhangs occur at eaves and other projecting sections,
where the wind has access, the positive vertical wind pressure must
be added to the eaves suction load to obtain the total load.
On large projects which take some time to complete, consideration
must be given to the risk of wind damage which may occur to partially
clad buildings during adverse weather conditions.
There are natural variations of wind speeds and directions by region
and by season. The South African seasonal wind charts below (as
published by the South African Weather Services) give data which
could assist in the initial assessment of fastening and installation
details.
STORAGE, HANDLING AND MAINTENANCE
MODEK sheets are usually supplied loose to local South African destinations.
In some cases sheets can be bundled, wrapped and strapped for ease
of handling.
Storage:
MODEK sheets must be stored on clean battens or pallets laid on
firm, level ground, under cover. Batten centres should not exceed
1.5 metres.
If it becomes necessary to store MODEK sheets outside, the duration
of this storage should be kept to a minimum, and the MODEK sheets
must be protected using opaque waterproof covers. If moisture is
allowed to collect between sheets, the solar energy passing through
the sheets is intensified, (as in a "solar battery") causing
the moisture to boil. This will result in premature discolouration
of the MODEK sheets.
Handling and Cutting:
Take extra care when handling MODEK PC sheets, as their resistance
to scratching is low.
MODEK GRP sheets can be cut with a fine toothed hacksaw, angle grinder
with standard masonry cutting disc or 40 / 60 grit diamond blade.
MODEK PC sheets can be cut with a tungsten-tipped circular saw blade.
Sheets can be notched with standard metal snips.
Holes may be drilled with standard high speed steel bits, and not
punched. Protective gloves and eye protection should be worn when
handling, cutting or drilling MODEK sheets. Dust protective masks
should be worn when cutting sheets.
Maintenance:
Regular maintenance should be carried out in order to maintain designed
light transmission of MODEK roof sheets. Periodically clean MODEK
sheets using warm water and detergent, and wash down with fresh
water. Periodically inspect fastenings and flashings and re-tighten
or renew as necessary.
TYPICAL EXAMPLE OF AN ARCHITECTURAL TECHNICAL
SPECIFICATION
MODEK
TRANSLUCENT PROFILE SHEETS
GRP / Ampagard Polycarbonate translucent sheeting to suit ______________
profile as manufactured by MODEK. |
GRP
The sheeting is to be manufactured in strict accordance with
the South African Bureau of Standards specification No. 1150/1984
and is to carry the mark of approval.
The weathering surface is to be coated with a UV stabilised
gelcoat. MASS,
COLOUR AND TRANSLUCENCY
GRP
The sheeting to be of nominal mass of ______________ kg/m2
and of a ______________ colour permitting a light transmission
of ______________%. |
AMPAGARD
POLYCARBONATE
The sheeting is to be extruded using a sheeting grade of polycarbonate
polymer, and shall have a co-extruded weathering surface layer
of UV grade polycarbonate polymer. THICKNESS,
COLOUR AND TRANSLUCENCY
AMPAGARD POLYCARBONATE
The sheeting to be of nominal thickness of 1.25 mm and of a
______________ colour permitting a light transmission of ______________%.
|
NATIONAL BUILDING REGULATIONS - SABS 0400
The following extracts from the NBR SABS 0400 give further insight
into the following areas relating to translucent roof sheeting when
used in a building:
- Special
provision of natural lighting with the associated "deemed-to-satisfy"
rules (pages 101 -102).
- The
regulations pertaining to the use of combustible roof coverings
on a building (pages 175-176).
- Those
building materials deemed to be non-combustible (page 207).
From this
it is appropriate that both PC and GRP be considered to be combustible
materials, notwithstanding the different attributes of the two materials
in a fire. |